Undervoltage protection to the motor starter.
Technical parameters:
- Rated operating voltage: 220 ÷ 240, 380 ÷ 415 V ac
- Rated frequency: 50 Hz
- Power consumption at power-up: 7.5 VA / 4.3 W
- Holding power: 3.8 VA / 1.3 W
- Mounting: front mounting under the motor starter cover
- Connection: cross section - 2x 0.35 mm2, length - 230 mm.
- Accessories for: SM1E
- To switch off the motor starter in the event of a voltage loss even in the event of a gradual voltage drop between 70% and 35% Ue.
- To switch off the motor starter when the button is pressed (NC contact).
- To prevent the engine starter from turning on if the voltage is less than 35%.
- To protect against motor restart after a power failure.